  • Profile:

    KD7T42、KD7T42P Spring type quick closing butterfly valve is widely used in gas waste heat power generation system and extraction steam heating steam turbine system. As the guarantee of system safety, this kind of valve has been widely used.

Product description

KD7T42、KD7T42P Spring type quick closing butterfly valve is widely used in gas waste heat power generation system and extraction steam heating steam turbine system. As the guarantee of system safety, this kind of valve has been widely used. It can replace the electric stop valve and check valve in the original system design because of its excellent performance such as quick closing, flow resistance and sealing.

Product use

This valve is mainly used in parallel units of thermal power plant and gas waste heat generator set, as an emergency shut-off valve to protect the safety of the system.

Product features

1. The fast closing time can reach 0.5 seconds, and the emergency cut-off is safe and reliable.
2. Three eccentric metal seal, seal structure, light and flexible opening and closing, sealing zero leakage.
3. Double eccentric soft sealing structure can be selected for normal temperature medium, with low cost and reliable sealing.
4. Close the valve end buffer, effectively avoid the valve inertia impact.
5. Spring can be used to realize quick closing, and accumulator can be used to realize quick closing of liquid. The two forms are the same, and they are also safe and reliable.

Dimensional drawing

Connection size
KD7T42、KD7T42P Connection dimensions of spring type quick closing butterfly valve(mm)
DN P L L1 L2 H1 H2 Flange connection size
400 0.6 216 966 1449 320 780 GB/T17241
DB/T9113
1.0 216 966 1449 330 785
1.6 216 966 1449 345 800
450 0.6 222 966 1449 370 805
1.0 222 966 1449 380 810
1.6 222 966 1449 395 835
500 0.6 229 966 1449 400 898
1.0 229 966 1449 410 898
1.6 229 966 1449 425 898
6000 0.6 267 966 1449 440 898
1.0 267 966 1449 460 920
1.6 267 1150 1820 470 1020
700 0.6 292 966 1449 436 950
1.0 292 1150 1820 550 1075
1.6 292 1150 1820 570 1100
800 0.6 318 1150 1820 625 1142
1.0 318 1150 1820 640 1158
1.6 318 1150 1820 660 1183
900 0.6 330 1150 1820 700 1190
1.0 330 1150 1820 710 1210
1.6 330 1150 1820 725 1239
1000 0.6 410 1150 1820 760 1250
1.0 410 1150 1820 770 1275
1.6 410 1360 2180 790 1306
1200 0.6 470 1150 1820 875 1360
1.0 470 1360 2180 890 1385
1.6 470 1360 2180 915 1418
1400 0.6 530 1360 2180 1000 1478
1.0 530 1360 2180 1020 1510
1.6 530 1360 2180 1045 1546
1600 0.6 600 1360 2180 1120 1599
1.0 600 1360 2180 1140 1639
1.6 600 1610 2520 1170 1738

 

matters needing attention

1. Before installation, check whether the specification, pressure, temperature and corrosion resistance of butterfly valve meet the use requirements. Check whether the parts are damaged or loose.
2. The butterfly valve can be installed on the pipeline at any angle and should be closed; when welding the pipe flange, the valve sealing port should be blocked with a plate to prevent particles and sundries from damaging the sealing surface. After welding, take down the valve, clean the valve sealing surface and pipe cavity, and then install the fixed valve.
3. Please pay attention to the pressure bearing direction when the valve is closed.
4. Before installation, the sealing surface (sealing surface at both ends, sealing surface of butterfly plate and sealing surface of valve seat) shall be thoroughly cleaned to remove dust and dirt.
5. Before installation, the butterfly valve should be air tested, and the opening and closing position should be flexible, and the opening and closing position should be consistent with the position indicated by the pointer.
6. Manual operation, clockwise is off, counter clockwise is on, pointer indication is in place, it is not allowed to open and close the valve with additional force.
7. During the pressure test of the valve, it is not allowed to use single flange for installation and pressure test, but double flange installation and pressure test must be adopted. The test pressure shall comply with GB / T13927-92.
8. The bolts shall be tightened symmetrically and alternately instead of separately.
9. The limit screw has been adjusted before delivery, so it is not allowed to adjust it easily. If the configuration of driving device is electric or pneumatic, please refer to the manual of supporting drive device.
10. When the electric butterfly valve leaves the factory, the opening and closing stroke of the control mechanism has been adjusted. In order to prevent the wrong direction when the power supply is connected, the user should first manually open it to the half open position before connecting the power for the first time, and then press the inching switch to check that the direction of the indicator wheel is consistent with the opening direction of the valve.
11. If the valve is found to be open and closed abnormally, the cause shall be found out for repair and elimination, so as to prevent the valve from being damaged due to opening and closing by means of applying force.